FD2WI SERIES - 2 HOUR FIRE-RATED ACCESS PANELS FOR WALLS - INWARD OPENING DOOR

An Access Panel with Inward-Opening Door for Applications with Tight Space Considerations

Materials: Painted galvanized steel or 304 stainless steel.

Frame: 16 ga (1.61mm) steel up to and including 30” x 48” or 14ga (1.99mm) steel for larger sizes. Depth “D”= 3-1/2” (89mm)

Trim: Width - 7/8” (22mm).

Door Panel: - 18 ga (1.31mm) with 22 ga (0.85mm) liner - Door widths up to 48” W.

Insulation: The door panel contains 1-1/2” (38mm) of high temperature insulation material.

Finishes: Electrostatically-applied rust-inhibitive off-white prime coat or a No. 4 polished stainless steel finish on exterior surface.

Hinges: The concealed piano hinge allows the door panel to open inward 90°.  The hinge is place on the "H" dimension.

Panel Closer: The automatic panel closer will close and latch the door from an open position of approximately 90° as required by code.

Latch: The standard factory installed latch is a flush mount 1/4” allen key. All fire-rated locks are self-latching and include an interior latch release mechanism allowing the doors to be opened from the inside. 

Sizes: Minimum 16" x 16"

This model of wall and ceiling fire-rated panels is manufactured under the factory inspection service of Intertek Warnock Hersey) and have a label reading: “Listed access frame and insulated fire door assembly 2 hour fire rating. Vertical Installation. Temperature rise maximum 139° C / 250° F at 30 minutes, 250° C / 450° F at 60 minutes.”